Gebruiksaanwijzing /service van het product 05176-0 van de fabrikant Generac Power Systems
Ga naar pagina of 52
PO WER SY STEMS, INC. ® Installation and Owner’ s Man ual Air -cooled A utomatic Standb y Generators Model: 05176-0 (13 kW NG, 15 kW LP) D ANGER DEADL Y EXHAUST FUMES. OUTDOOR INST ALLA TION ONL Y!! Not intended f or use as Primary P ower in place of utility or in life-support applications.
I NTRODUCTION Thank you for purchasing this model by Generac P ower Systems Inc.. This model is a compact, high performance, air - cooled, engine - driven generator designed to automatically supply electrical power to operate critical loads during a utility power failure.
T able of Cont ents Air-cooled 1 5 kW Generators 1 Introduction ........................ Inside F ront Cover Read This Manual Thoroughly ........................ IFC Contents .......................................................... IFC Operation and Maintenance .
2 Study these SAFETY RULES carefully before install- ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained.
3 ELE CTR ICAL HA Z AR DS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion.
D ANGER Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. 1.1 U N P ACKING/I NSP ECTION After unpacking, carefully inspect the contents for damage.
Section 1 — General Information Air-cooled 1 5 kW Generators 5 1.4 TH E GEN ER A T OR Exh aust En c lo su r e O il Filte r Batter y Com p artmen t F uel Inl et C ontro l P a n el D a t a D ecal O i l Di p stic k F uel Re g ulato r Com p osite Bas e Figure 1.
6 Section 1 — General Information Air-cooled 1 5 kW Generators 1.5 SP E CI F ICA TIONS 1.5.1 GEN ERA T OR Rated Max. Continuous P ower Capacity (W atts*) .......................... 13,000 NG/15,000 LP Rated V oltage..................................
7 4. Remove the engine air in baffle located on the left - hand side of the battery compartment. T wo M6 screws are located on top of the baffle and two M6 screws are located on the inside of the baffle towards the back. 5. Remove the small hose clamp and hose from the fuel regulator .
Remote monitoring functions are only available with the A UTO/OFF/MANU AL switch in the Auto or Manual position. Since the contacts are SPDT , it is possible to monitor either state of each alarm function.
9 Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol- lows 1. Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2.
10 Figure 2.4 – Battery Cable Connections NOTE: The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation.
11 3. Check utility power source voltage across termi- nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line -to - neutral voltage should be 120 volts AC.
12 3.5 CH E CKI NG AUT OMA TIC OP ER A TION T o check the system for proper automatic operation, proceed as follows: 1. Set the generator’s main circuit breaker to it ’s OFF (or open) position. 2. Check that the AUTO/OFF/MANU AL switch is set to OFF .
13 Section 3 — Post Installation Start-up and Adjustments Air-cooled 1 5 kW Generators 7. T urn utility power to the main distribution panel back on. This can be done by switching the ser - vice main breaker to the on or closed position. Allow the generator to shut down.
14 Section 4 — Operation Air-cooled 1 5 kW Generators 4.1 USI NG TH E AUT O/OF F/MAN UAL SWIT CH (F IGU R E 4.1) 4.1.1 “ AUT O” POSITION Selecting this switch position activates fully automatic system operation.
15 • Retransfer to utility power source then occurs. F . Engine Cool- down Timer • When the load is transferred back to utility power source, the engine cool- down timer starts tim- ing . • The timer will run for about one minute, and the generator will then shut down.
16 4.4.2 CL OSE T O EM ERGENCY SOURCE SI DE Before proceeding, verify the position of the switch by observing the position of the manual operation handle in Figure 4.2. If the handle is DOWN , the contacts are closed in the EMERGENCY (ST ANDBY) position.
17 7. Move the switch's main contacts back to their UTILITY position. F or example, load connected to UTILITY power supply . Refer to "Manual Operation".
18 4.8.3.1 Approximat e Crank Cycle Times • 15 seconds ON • 7 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 4.8.4 OVERSPEED This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit.
19 Figure 5.3 – Oil Drain Hose and Filter Oil Filter Oil Drain Ho s e L o o s e n 3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip. 4. Refill with the proper recommended oil (see "Changing the Engine Oil").
20 5.7 B A T TER Y MAI NTENANCE The battery should be inspected per the “Service Schedule”. The following procedure should be fol- lowed for inspection: 1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary .
21 When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
22 5.1 2.2 R ETUR N T O SERVICE T o return the unit to service after storage, proceed as follows: 1. Set the generator’s main circuit breaker to its OFF (or OPEN) position. 2. V erify that utility power is turned off and that the A UTO/OFF/MANU AL switch is set to OFF .
23 Section 5 — Maintenance Air-cooled 1 5 kW Generators 7 KW - 40 KW SMALL ST ANDBY GENER A T OR SET S F ollowing is a recommended maintenance schedule for small standby and residential generator sets from 7 kW to 40 kW in size, and applies to gas engine driven units.
24 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 T asks Recom- T ask T ask Required T ask T ask Required T ask mended Comp. Comp. to be done Comp.
25 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 T asks Recom- T ask T ask Required T ask T ask Required T ask mended Comp. Comp. to be done Comp.
26 Maintenance Level 1 Level 2 Level 3 Level 4 Level5 T asks Recom- T ask T ask Required T ask T ask Required T ask mended Comp. Comp. to be done Comp.
27 Section 6 — T roubleshooting Air-cooled 1 5 kW Generators 6.1 TROU B LE SHOO TI NG GU I DE Problem Cause Correction The engine will not crank. 1. F use blown 1. Replace 15A fuse on generator control panel. 2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary .
28 Section 7 — Mounting Dimensions Air-cooled 1 5 kW Generators Drawing No. 0F592 7.
29 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Wiring Diagram – Drawing No. 0F5 643-B Part 1 TR - RELAY , TRANSFE R CUS T O MER SU PPLIE D BLA CK BATTERY 12V 0 HT O S P 2 S P 1 L OP 0.
G R D G R D 22 5 22 5 224 224 1 5 224 225 0 2 39 1 5A 66A 2 3 1 94 4 14 0 22 5B 224B 1 3A 0 1 1 C L OS E S T T O BEARIN G 0 66 77 4 4 0 F2 1 5 1 3 RE GU LAT OR V O LTA GE 1 94 2 3 N1 N1 4 66A N2 351 N.
31 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Wiring Diagram – Drawing No. 0F5 643-B Part 3 G R D CO M + RY5- RY1+ RY 3+ RY4- COM - RELAY B O AR D S I G NAL S REM O T E N1 N2 F4 1 94.
32 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Electrical Schematic – Drawing No. 0F5844-B C HAR G E R BATTERY 1 62 22 V O LTA GE RE GU LAT OR ELE C TR O NI C 6 4 0 11 ( STATOR ) DPE .
33 Section 8 — Electrical Data Air-cooled 1 5 kW Generators Electrical Schematic – Drawing No. 0F5844-B SM C 1- 1 C 1- 5 SCR 0 0 0 1 6 0 1 8 D D IM2 IM1 S P 2 S P 1 1 6 0 SC 0 S W 1 1 5A 1 5 1 94 .
34 47 54 7 2 2 2 0 49 4 9 4 3 43 36 4 37 2 5 35 32 34 35 2 6 53 74 4 6 51 8 7 8 80 39 81 1 8 52 44 63 1 5 51 2 1 71 69 42 1 0 41 7 3 49 9 51 4 9 11 0 72 7 9 5 2 7 35 4 9 44 5 56 1 57 1 9 52 47 4 0 69 .
35 ITEM P ART NO . QTY . DESCRIPTION 1 0C6140 1 A SS EMBL Y , ENCLO S URE BA S E 2 0C67 3 5 2 S UPPORT , ROOF FOLDING 3 0F006 3 1 ENCLO S URE, FRONT 4 0C7062 1 ENCLO S URE, EXHA U S T S IDE 5 0F562 9 .
36 3 1 19 3 7 38 22 8, 9 27 45 46 44 28 47 10 25 3 2 5 14 13 17 23 34 15 21 35 20 4 15 29 5 13 38 6 7 23 25 12 27 40 41 36 39 45 44 43 1 30 15 11 47 45 24 45 47 50 49 48 5 1 53 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators Control Panel – Drawing No.
37 ITEM P ART NO . QTY . DESCRIPTION 1 0E7 88 6G 1 CIRCUIT BREAKER 70A X 2P 240V (15KW) 2 0A1 8 01 1 A SS EMBL Y , BA TTER Y CHARGER ENGINE 3 0 83 04 9 1 A SS EMBL Y , POTTED REGULA TOR 4 0C2174 1 REL.
38 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators GT -990 Eng ine – Drawing No. 0E8 7 7 4-Q Part 1.
39 ITEM P ART NO. QTY . DESCRIPTION 1 0C572 9 1 A SS EMBL Y , CRANKCA S E HOU S ING WITH S LEEVE 2 0E 98 4 3 1 S EAL, 38 I.D . CRANK S HAFT 3 0 9 0 388 3 S CREW , T APTITE M6-1.
40 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators GT -990 Eng ine – Drawing No. 0E8 7 7 4-Q Part 2.
41 ITEM P ART NO. QTY . DESCRIPTION 74 0C51 3 6A 2 KNOB, AIR CLEANER 75 0C 3 024 1 CO VER, AIRBO X NG/LP 76 0C 3 040 1 PRE-CLEANER, 77 0C 8 127 1 ELEMENT , AIR CLEANER 7 8 0D 8 564A 1 A SS EMBL Y , MIXER/AIRBOX 99 0 0D 8 564B 1 A SS EMBL Y , MIXER/AIRBO X 760 7 9 0D25 9 5 4 S CREW S HOULDER ( 8 MM) M6-1.
42 2 9 3 6 3 4 11 2 3 5 24 4 3 21 7 1 3 33 12 38 17 3 2 3 1 2 8 3 1 20 1 9 10 17 15 3 2 16 22 39 4 9 8 6 3 7 14 3 2 40 1 3 2 24 25 10 3 0 1 9 26 2 8 27 2 8 3 2 3 1 41 10 1 8 3 6 2 8 3 5 41 2 9 42 3 6 3 6 3 5 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators 1 5 kW Generator – Drawing No.
43 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators 1 5 kW Generator – Drawing No. 0D34 1 7 -L ITEM P ART NO . QTY . DESCRIPTION 1 0C6 93 4 1 AD APT OR, ENGINE 2 0C7 93 0 1.
44 7KW 17 12 2 8 11 20 10 25 21 24 1 9 2 3 22 22 15 26 14 1 3 16 2 9 1 8 8 2 8 12 3 2 10 11 27 3 1 4 5 3 2 10 17 1 26 15 14 16 1 3 3 7 1 9 9 3 0 21 25 20 24 2 9 1 8 2 3 11 12 2 8 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators Gas Regulator – Drawing No.
45 ITEM P ART NO . QTY . DESCRIPTION 1 0D56 9 4 1 CA S TING, TWIN REGULA T OR HOU S ING 2 0F5022 1 S OLENOID COIL, 12VDC 3 0C4647 1 GA S KET , S OLENOID 4 0D4166 1 PLUNGER, LP REGULA TOR A SS EMBL Y 5 0C6070 1 S PRING- S OLENOID , PLUNGER 8 0F47 9 5 4 S CREW PPHM S EM S M4-0.
46 Section 9 — Exploded Views and P arts Lists Air-cooled 1 5 kW Generators T ransfer Switch – Drawing No. 0F563 3$-A.
47 ITEM P ART NO . QTY . DESCRIPTION 1 0D 9 61 8 1 TR S W- H S B 200A 2P 250V 2 0E 33 75 6 LUG S LDL SS 250-#6 AL/CU 3 0F1252 6 S CREW BH S C 1/4-20 X 3 / 8 4 0220 9 7 6 W A S HER LOCK M6-1/4 5 074 9 0 8 5 S CREW HHTT M5-0. 8 X 16 BP 6 045771 1 NUT HEX M 8 -1.
48 CALI FOR N IA EM IS SION CONTROL W ARR ANT Y ST A TEM ENT Y OUR W AR R ANTY R IGHTS AND OB LIGA TIONS The California Air Resources Board (CARB) and Generac P ower Systems, Inc. (Generac) are pleased to explain the Emission Control System W arranty on your new engine.
49 EM IS SION CONTROL S Y STEM W AR RANT Y Emission Control System W arranty (ECS W arranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines.
Part No. 0F5631 Revision C (12/07/06) Printed in U.S.A. Section 1 0 – W arranty Air-cooled 1 5 kW Generators GENERA C PO WER SYSTEMS ST ANDARD LIMITED W ARRANTY FOR HOME ST ANDBY/LIGHT COMMERCIAL PR.
Een belangrijk punt na aankoop van elk apparaat Generac Power Systems 05176-0 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Generac Power Systems 05176-0 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Generac Power Systems 05176-0 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Generac Power Systems 05176-0 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Generac Power Systems 05176-0 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Generac Power Systems 05176-0 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Generac Power Systems 05176-0 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Generac Power Systems 05176-0 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.