Gebruiksaanwijzing /service van het product 004988-4 van de fabrikant Guardian Technologies
Ga naar pagina of 48
Owner’ s Man ual ONL Y QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD A TTEMPT INST ALLA TION!! This manual should remain with the unit. Liquid-cooled, Prepac kaged Standb y Generator s Model Number: .
2 I NTRODUCTION Thank you for purchasing this model of the standby generator set. Every effort was expended to make sure that the information and instructions in this manual are both accurate and current at the time the manual was writ - ten.
T able of Cont ents Liquid-cooled 30 kW Generators 1 INTRODUCTION ............................................... IFC SAFETY RULES .................................................... 2 Section 1 — GENERAL INFORMA TION ............. 4 1.1 Generator .
2 Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The gen- erator can operate safely , efficiently and reliably only if it is properly installed, operated and maintained.
3 • Inspect the generator regularly , and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts. • Before performing any maintenance on the generator , disconnect its battery cables to prevent accidental start -up.
4 1.1 GEN ER A T OR This equipment is a liquid- cooled, engine - driven generator set. The generator is designed to supply electrical power that operates critical electrical loads during utility power failure. The unit has been facto - ry-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only .
5 1.6 GEN ER A T OR F U EL SYST E M The unit has been factory tested and adjusted using a natural gas fuel system. If propane (LP) gas is neces- sary , contact an authorized service dealer . F uel pressure for a natural gas set up should be five inches to 14 inches of water column (0.
6 Figure 1.6 - Low Coolant Level Sensor 1.7 .4 OVERSPEED SHUTDOWN The engine control board receives AC frequency sig - nals from an engine run winding in the alternator . Should AC frequency exceed about 72 Hertz for three seconds or 75 Hertz instantaniously , the engine shuts down and the overspeed LED turns on.
1.1 0 SP ECIF ICA TIONS 1.1 0.1 GEN ER A T OR SP ECIF ICA TIONS 1.1 0.2 ENGI N E SP ECIF ICA TIONS Make ........................................................................................................F ord Displacement ........................
8 1.1 3 T ORQUE SP ECIF ICA TIONS Cylinder Head ............................................ 15 (+ 90° + 90°) ft.lb . Intake Manif old ................................................................ 13 ft.lb. Exhaust Manifold ......................
9 • NFP A No. 37, ST A TIONARY COMBUSTION ENGINES AND GAS TURBINES. • NFP A No. 76A , ESSENTIAL ELECTRICAL SYSTEMS FOR HEAL TH CARE F ACILITIES. • NFP A No. 220, ST ANDARD TYPES OF BUILDING CONSTRUCTION • NFP A No. 68, GUIDE FOR EXPLOSION VENTING • NFP A No.
10 2.5 EM ERGENCY CI RCUIT ISOLA TION M E THOD This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator . If the generator can only power criti- cal loads, within it ’s wattage/amperage capacity , dur - ing utility power outages, use the emergency circuit isolation method.
11 Control system interconnections consist of N1 and N2, and leads 23 and 194. Control system intercon- nection leads must be run in a conduit that is sepa- rate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below: 2.
12 2.1 1.1 P RIOR T O I N ITIAL S T ART -U P Prior to initially starting the generator , it must be properly pr epared for use. Any attempt to crank or start the engine before it has been properly serviced with the r ecommended types and quantities of engine fluids (oil, coolant, fuel, etc.
13 MANU AL — The control board will start and run the generator whenever the switch is in the manual position. AUT O — The control board will monitor the two - wire start circuit. When a two -wire start is issued the control board will immediately start and run the gen- erator .
14 The system ready LED will be OFF when the switch is in the manual or OFF positions. The system ready LED is also used to indicate the presence of utility sensing at the PCB when the switch is either in the A UTO or MANU AL modes.
15 3.7 WEEKL Y EXERCISE CY CLE The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.
16 4.3 O VER L O AD P RO TE CTION FOR ENGI N E DC ELE CTR ICAL SYSTE M Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.
17 4.5.8 CH ECK F AN B EL T • Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt. • Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 inch.
18 4.5.1 2 SP AR K P L UG S Reset the spark plug gap or replace the spark plugs as necessary . See Section 6. 1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent.
19 D ANGER Storage batteries give off explosive hydr ogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury .
20 Section 4 — Maintenance Liquid-cooled 30 kW Generators 4.7 S CH EDU LED MAI NTENANCE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application.
21 Section 4 — Maintenance Liquid-cooled 30 kW Generators Maintenance Level 1 Level 2 Level 3 Le vel 4 T asks Recom- T ask Required T ask Required T ask T ask mended Comp .
22 Section 4 — Maintenance Liquid-cooled 30 kW Generators Maintenance Level 1 Level 2 Level 3 Le vel 4 T asks Recom- T ask Required T ask Required T ask T ask mended Comp .
23 Section 5 — T roubleshooting Liquid-cooled 30 kW Generators TROU B LE SHOO TI NG POI NT S P ROBLEM CAUSE CORR E CTION Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. Loose or corroded or defectiv e 2. Tighten, clean or replace battery cables.
24 Section 6 - Notes Liquid-cooled 30 kW Generators.
25 Section 7 — Installation Diagram Liquid-cooled 30 kW Generators Installation Diagram — Drawing No. 0E8695.
BRUSH ASSEMLY ( GENERATOR ) A U T O MATI C V O LTA G E RE GU LAT OR BULKHEAD CONNECTOR 1 ( ENGINE ) CIRCUIT BREAKER ( EXCITATION ) FUSE, BAT. POWER ( 15A AGC TYPE ) CIRCUIT BREAKER ( OUTPUT ) DIODE [ .
27 LEGEND [ CONT. ]: J -2 - L OS - S M - J B - WL S - H C T - J -1 - IM - I C - ELE C . GO VERN O R A C T U AT OR GROUND ( SENSING/LOW AMP ) GROUND ( POWER/HIGH AMP ) D. C . C HAR G E ALTERNAT OR S TARTER CO NTA C T OR CONNECTOR 1 ( ENGINE ) DRIVER ELE C .
28 Section 8 - Electrical Data Liquid-cooled 30 kW Generators Electrical Schematic — Engine — Drawing No. 0E6200-B A U T O MATI C V O LTA G E RE GU LAT OR BRUSH ASSEMLY ( GENERATOR ) CIRCUIT BREAK.
29 Section 8 - Electrical Data Liquid-cooled 30 kW Generators Electrical Schematic — Engine — Drawing No. 0E6200-B SC - I C - IM - L OS - S M - WL S - LEGEND [ CONT. ]: CONNECTOR (C1) SWITCH , HIGH COOLANT TEM P C RANKIN G CO NTA C T OR D. C . C HAR G E ALTERNAT OR CONNECTOR 1 ( ENGINE ) DRIVER ELE C .
MOUNTING BA S E CONT ACT OR WIRE HARNE SS 7 5 6 16 ENGINE FOO T 2 4 3 41 40 16 7 6 5 35 9 13 17 12 8 18 16 43 BLOCK ENGINE 30 TO 44 35 34 39 36 33 44 42 22 20 32 38 18 31 20 21 TO S T ARTER S T ARTER .
ITEM P ART NO . QTY . DESCRIPTION 1 0E5822 1 BA S EFRAME, WELDMENT 3.0L FORD 2 052860 4 NUT FLANGED HEX M12-1.75 3 052251 4 D AMPENER VIBRA TION 40 BLUE 4 052257 4 S P ACER .49 X .62 X 1.87 PWDR/ZNC 5 052252 4 D AMPENER VIBRA TION 6 052259 4 W A S HER FLA T M12 7 052891 4 S CREW HHC M12-1.
32 3 7 S TATE S F O AM I S O N FAR S IDE S TATE S F O AM I S O N NEAR S IDE 17 L AT C H DETAIL 3 0 3 1 3 4 38 2 3 2 3 4 27 4 3 1 8 40 4 7 "B " 11 S EE LAT C H DETAIL 25 5 2 9 6 4 9 4 8 5 TO "A" T YPI C AL O F R OO F PANEL THAT R E Q UIRE INSULATION.
33 ITEM P ART NO . QTY . DESCRIPTION 1 0E8411 1 INT AKE DUCT H S B 2 0E8042 1 DUCT DI S CHARGE RH FRONT 3 0E8041 1 DUCT DI S CHARGE LH FRONT 4 0C2454 62 S CREW TH-FRM M6-1 X 16 N W A Z/J S 5 0E8402 1 .
34 Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Control Panel — Drawing No. 0E7 11 8-K.
35 ITEM P ART NO. QTY . DESCRIPTION 1 0E7195 1 CONTROL BO X H S B 2 0E7196 1 CO VER FRONT P ANEL H S B 3 0E7197 1 CO VER T OP P ANEL H S B 4 0E7193 1 DECAL W ARNING S H S B 5 0E7194 1 DECAL CONTROL S .
11 65 17 57 24 61 60 30 25 58 35 39 36 WIRE GROUND 39 32 31 35 79 24 50 54 53 43 2 42 38 61 53 51 14 55 60 25 85 57 58 87 69 36 & REPLACE REMO VE 35 39 86 68 66 67 32 16 18 19 80 48 47 42 41 44 45.
ITEM P ART NO. QTY . DESCRIPTION 1 0E6201 1 ENGINE 3.0L FORD (FD) (MAKE) 2 0E8824 2 S T AMPING ENG FOOT 3.0L FORD 3 0E8963 1 PULLEY CRANK S HAFT 3.0L FORD RD 4 0E9020 1 BRACKET DC AL T 3.0L FORD 5 0A1232 1 D .C. AL TERNA TOR A SS Y 6 0A7801B 1 PULLEY POL Y -V 82 OD .
38 27 FRAME 11 10 9 12 3 8 9 26 25 "A" 20 21 TO WA T ER 12 4 PUMP 6 15 17 7 13 1 15 3 5 24 22 23 2 24 12 31 28 32 12 T O "A" 18 14 HOU S ING THERMO S TAT TO 29 12 33 35 30 ENGINE 12 TO Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Radiator — Drawing No.
39 ITEM P ART NO . QTY . DESCRIPTION 1 0E9947 1 RADIA T OR R-IN,L-OUT 658X489X49 2 0E6340 1 VENTURI 3.0L FORD H S B 3 0E8531 2 S IDE S UPPORT RADIA TOR H S B 4 0E6398 1 TUBE LOWER RAD 3.0L FORD H S B 5 0F6630 1 HO S E RADIA TOR UPPER 6 080713 1 BRACKET COOLANT T ANK 7 076749 1 T ANK COOLANT RECOVER Y 8 049814 4 S CREW HHC M10-1.
40 28 "B" 31 10 16 4 2 17 5 9 1 7 6 29 32 30 11 29 13 15 8 3 12 6 13 AIR TO CLEANER 34 33 29 14 T O "B" 19 26 27 18 43 41 40 21 28 20 26 25 42 39 Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Fuel Syst em — Drawing No.
41 ITEM P ART NO . QTY . DESCRIPTION 1 * --------- 1 WELDMENT MOUNTING BA S E 2 075580 1 FLANGE FUEL INLET 3 0E7691 1 A SS Y REGULA TOR 3.0L NG OR LPV 4 039253 2 S CREW HHC M8-1.25 X 20 G8.8 5 022145 2 W A S HER FLA T 5/16 ZINC 6 022129 4 W A S HER LOCK M8-5/16 7 045771 2 NUT HEX M8-1.
42 3 LOCKTIGHT LOCKTIGHT 7 15 17 8 7 6 18 4 16 LEAD S 5 2 9 13 21 19 20 14 10 11 12 30 1 31 Section 9 - Exploded Views and P arts Liquid-cooled 30 kW Generators Alternator — Drawing No.
43 ITEM P ART NO . QTY . DESCRIPTION 1 0F1659A 1 RO TOR 390 15KW 1P DIRECT H S B (2.5L FORD) 0F1657A 1 ROT OR 390 20KW 1P DIRECT H S B (2.5L FORD) 0F1655A 1 ROT OR 390 25KW 1P DIRECT H S B (2.5L FORD) 0F5073A 1 ROT OR 390__30AD1 H S B TECUM 0E7413A 1 RTR 390 40KW 1P DIRECT H S B 2 0F1660A 1 S TR 390 15AD H S B (382MM LONG) (2.
ITEM P ART NO. QTY . DESCRIPTION 1 0F0738 1 MUFFLER 7"X9"-(2)2"IN/2.5"OUT 2 0F6258 1 PIPE MUFFLER OUT 3 044149 2 GA S KET EXHA U S T RING 4 0F1008 1 EXHA U S T PIPE LH 3.0L H S B 5 0F1009 1 EXHA U S T PIPE RH 3.0L H S B 6 039288 1 S CREW HHC M8-1.
45 ITEM P ART NO . QTY . DESCRIPTION 1 0E5193 1 PLA TE AIR CLEANER AD APTER 2 0E0519A 1 ADAPTER CARB URETOR W/PVC CONN 3 049226 4 W A S HER LOCK M5 4 049815 4 S CREW HHC M5-0.
Part No. 0F6866 Revision 0 (07/26/05) Printed in U.S.A. Section 1 0 – W arranty Liquid-cooled 30 kW Generators GENERA C PO WER SYSTEMS "TWO YEAR" LIMITED W ARRANTY FOR GU ARDIAN ® "P.
Een belangrijk punt na aankoop van elk apparaat Guardian Technologies 004988-4 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Guardian Technologies 004988-4 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Guardian Technologies 004988-4 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Guardian Technologies 004988-4 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Guardian Technologies 004988-4 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Guardian Technologies 004988-4 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Guardian Technologies 004988-4 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Guardian Technologies 004988-4 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.