Monitoring For Bu siness-Critical Con tinuit y Li eb er t O p en Com m s ™ EM User Ma nual.
.
i T ABLE OF CONTENTS 1.0 I NTRODUCTI ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii 5.0 G ETTING S TA R T E D W ITH THE W EB I NTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 5.1 Open the Web Interface and Log In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 5.
iii FIGURES Figure 1 Front view (EM PDU & vEM-14 controlle rs shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Figure 2 Rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iv.
Introd uction 1 1.0 I NTRODUCTION The Liebert OpenComms™ EM is a compact, half-duplex de vice designed t o mo nitor temperature, humidity, water dete ction and contact closure and not ify pe rsonnel when those con ditions exceed user-defined limits.
Introd uction 2 1.1 Overview The OpenComms EM features indicator li ghts on the front, as shown in Figure 1 . Figure 1 Front view (EM PDU & vEM-14 contr ollers shown) 1.1.1 Dimensions and Mounting Overview - EM & EM PDU Controll ers • The unit is 4.
Introd uction 3 1.1.3 Connectors on Back of Unit The back of the OpenComms E M, shown in Figure 2 , has an input p ower so urce, sensor ports, a modem port and an Ethernet port. The EM PDU an d vEM-14 controllers have serial ports, and vEM-14 controllers also have 10 dry contact inputs.
Introd uction 4 1.2 Indicators The front of the OpenComms EM has in dicators that show input power to the unit and the status of various connections, as shown in Figure 3 and descri bed in Table 2 .
Installation 5 2.0 I NST ALLATION This section provides instru ctions for installing, mounting and connecting power and other cables to the OpenComms EM. 2.1 Inst allation Considerations The OpenComms EM must be installed indoors where el ectrical service is available.
Installation 6 2.2 Decide on Placement of the OpenComms EM The unit may either be placed on a level surface or mounted on a w all, depending on the user’s appli- cation and the location of equipm ent to be connected and monitored. vEM-14 controllers may also be mounted in a rack.
Installation 7 2.2.2 Mounting the Unit on a W all or in a Ra ck (vEM-14 Controllers) The vEM-14 controller may be mounted on a wall or in a rack, such as the Liebert Foundation.
Installation 8 2.3 Make Connections All ports are on the back of the OpenComms EM. The port placement and port labels diff er for each model. Refer to Figure 2 for your mode l. 2.3.1 Connect Power to the Unit • Connect the DC power adapter to the DCN/Powe r po rt on the back of the OpenComms EM, as shown in Figure 2 .
Assign an IP Address 9 3.0 A SSIGN AN IP A DDRESS After connecting the OpenComms EM device to your networ k, the next step is to iden tify the device to the network by assigning an IP address.
Assign an IP Address 10 3.2 Use ARP to Assi gn an IP Address This method may be preferable if you are not usi ng a Microsoft host. To use the ARP command: 1. Open a command prompt. In Wind ows, one way to do this is: • Click on the Start button, then on Run .
Web Interface Overview 11 4.0 W EB I NT ERFACE O VERVIEW This section provid es a quick look at th e OpenComms EM Web interface and the viewing and con figu- ration functions accessi ble through tabs at th e top of the window. For step-by-step instruct ions on using the Web interface, proceed to 5.
Web Interface Overview 12 4.2 T abs The tabs at the to p right of the Web inte rface wi ndow provide access to al l the functions of the OpenComms EM device.
Web Interface Overview 13 4.4 Thresholds in the W eb Interface The OpenComms EM collects data from conne cted se nsors at regular intervals. When a reading crosses a user-defined threshold: • The sensor’s status changes. • Alerts are sent—if the unit is confi gured for e-mail, pager or SNMP trap alerts.
Web Interface Overview 14 4.4.3 MP Advanced Power S trip Thresholds When using the OpenComms EM to monitor MP Advanc ed Power Strips, you ma y set thresholds that will trigger alerts for power, voltage, current and temperatur e sensors in each power strip.
Web Interface Overview 15 4.5 Sensor Names and S t atus The Web interface displays four items ab out sensor s in all windows available through the Summary, Sensors and Power tabs, as shown in Table 10 . The sensor’s Name is an optional user-d efined description; the Description is created at the factory and cannot be changed.
Getting Started W ith the W eb Interface 16 5.0 G ETTING S T ARTED W ITH THE W EB I NTERFACE Once the unit is properly installed, you can view its Web interface usin g an Internet browser.
Getting Started W ith the W eb Interface 17 5.2 V iew Summary Dat a The Summary window provides a quic k look at the current status of all conn ected devices, as shown below. This window also has a Log Out button to exit the Web interface. To access the Summary window, log in (see 5.
Getting Started W ith the W eb Interface 18 5.3 Sensors Window The Sensors tab provides acces s to sens or-related data and settings, in cluding: • Setting thresholds that will tr igger alerts for each sensor (see 5.3.1 - Configure Sensors ) • Creating displa y names for any sensor (see 5.
Getting Started W ith the W eb Interface 19 5.3.2 Create or Change Sensor Names The Sensor Names feature allo ws you to create a name to help identify a sens or. This name is dis- played throughout the Web interface an d in notifications sent by pager or e-mail.
Getting Started W ith the W eb Interface 20 5.3.3 View Sens or Graphs The OpenComms EM sensor data may be viewed in gr aphic format, along wi th the sensor’s upper and lower alarm limits, as described i n 5.3.1 - Configure Sensors . The OpenComms EM stores up to 1,440 data sample s for each sensor.
Getting Started W ith the W eb Interface 21 Figure 6 Sensor graph - humidit y sensor example The line graph shows the selected senso r’s readings (black) chronologically from left to right—the most current reading is on the fa r right—as well as Warning (yellow) and Critical (red) limits.
Getting Started W ith the W eb Interface 22 5.4 Power Window (EM PDU & vEM-14 Controllers) The Power tab provides access to MP Advanced Po wer Strips connected to the OpenComms EM, including : • Turning receptacles on or off—all at once, individually or in pairs (see 5.
Getting Started W ith the W eb Interface 23 Link the Controls of T wo Receptacles Two receptacles may be linked for simultan eous cont rol. The receptacles may be on the same power strip or on two different power strips.
Getting Started W ith the W eb Interface 24 5.4.2 Configure Thresholds You may set thresholds that will tr igger alerts for power, voltage, current and temperature sensors in each power strip. To do this: • In the left side of the Power Data window, shown above, select a po wer strip (Port 1 or 2) .
Getting Started W ith the W eb Interface 25 5.4.3 View Power S trip Graphs Power strip data may be viewed in graph ic format, similar to those of sens or data. To access the Power Strip Graphs window (see 5.4.1 - Control Receptacles for more details): • Click on the Power tab at the top of the Web interfac e.
Getting Started W ith the W eb Interface 26 5.4.4 Create or Change Port Names The Port Names fe ature allows you to create a name to help iden tify a serial port. This name is dis- played throughout the Web interface an d in notifications sent by pager or e-mail.
Getting Started W ith the W eb Interface 27 5.5 Alert s Window The OpenComms EM may be configured to send alerts by e-mail or dial page rs to notify personnel when a sensor reading crosses a thre shold, either entering a warning or critical state or returning to normal status.
Getting Started W ith the W eb Interface 28 5.5.2 Modem Setup The OpenComms EM may be configured to send a numeric message to a pager. Note: The unit requires an ext ernal modem to send pager alerts. The modem port is set at 9600 baud, no parity, 8 data bits and 1 stop bit.
Getting Started W ith the W eb Interface 29 5.5.3 SNMP T rap Alert s Setup The OpenComms EM may be configured to send SNMP trap alerts to a computer whenever the status of a sensor changes from normal to a warning or critical state, a s well as a return-to-normal alert when the reading fall s within the normal range.
Getting Started W ith the W eb Interface 30 5.6 Security Window To protect configuration settings from unauthorized users, the Web interface allows you to set up users with different levels of access. • A user with Administration privileges has full access, including creatin g and modifying other user accounts.
Getting Started W ith the W eb Interface 31 5.6.2 Create a New User Account (Administrators Onl y) An administrator may create user accounts for up to 50 users, includ ing th e administrator account. Only users with administrative pr ivileges may create user accounts.
Getting Started W ith the W eb Interface 32 5.6.3 Modify an Existing Account (Administrators Only) Users with adm inistrative priv ileges may change all options on all users’ accounts , including their own. Users without administrative access are preven ted from chan ging anything except their ow n password; for details, see 5.
Getting Started W ith the W eb Interface 33 5.6.4 Change Password (Users with Read/Wr ite access) Users with Read or Read & Write access may change their password but no other user account infor- mation for their own accounts or those of other users.
Getting Started W ith the W eb Interface 34 5.7 Sys Info Window The OpenComms EM may be configured to send alerts by e-mail or dial page rs to notify personnel when a sensor reading crosses a thre shold, either entering a warning or critical state or returning to normal status.
Getting Started W ith the W eb Interface 35 5.7.2 SNMP Information To access the SNMP Information window, log in (see 5.1 - Open the Web Interface and Log In ) and: • Click on the Sys Info tab at the top of the Web interface, as shown below. • Click on the SNMP Information link on the left side of the wind ow.
Getting Started W ith the W eb Interface 36 5.7.3 Dat a Present ation To access the Data Presentatio n window, log in (see 5.1 - Open the Web Interface and Log In ) and: • Click on the Sys Info tab at the top of the Web interface, as shown below. •C l i c k o n t h e Data Presentation link on the left side of the wind ow.
Getting Started W ith the W eb Interface 37 5.7.4 Serial Ports To view the Serial Port 1 and 2 windows, log in (see 5.1 - Open the Web Interfac e and Log In ) an d: • Click on the Sys Info tab at the top of the Web interface, as shown below.
Pinout Guides 38 6.0 P INOUT G UIDES 6.1 Modem Setup and Pinout Guide The OpenComms EM must be connected to a modem to send pa ger alerts when a se nsor reading crosses a user-defined threshold (see 5.5.2 - Modem Setup for more information). The unit is compatible with modems that have DB9 or DB25 serial COM ports.
Downloadin g Firmware Updates 39 7.0 D OWNLOADING F IRMWARE U PD AT E S This section explains how to update the unit’s firmware. 1. The first step is to download the upgrade text file. To d o this, visi t Liebert’s Web site at http://www.liebert.com and go to the OpenComms EM section.
Specifications 40 8.0 S PECIFICATIONS T able 16 OpenComms EM specifications Power Requirement s EM & EM PDU controller vEM-14 controller NOTE Input 120 V AC, 60 Hz 12 0 V AC, 60 Hz If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
.
Ensuring The Hi gh Av ail abilit y 0f Mission-Critic al Dat a And Appli c ations. Emerson Net work P ower , the global leader in enabling business-critical continuity , ensures net work resiliency and.
Een belangrijk punt na aankoop van elk apparaat Liebert EM (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Liebert EM heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Liebert EM vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Liebert EM leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Liebert EM krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Liebert EM bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Liebert EM kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Liebert EM . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.