34003641FR/ AA - Page 1 T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R www.mgeups.com Installation and user manual Pulsar MX 4000 RT 5000 RT.
34008030EN /AA - Page 2.
34008030E N/AA - Page 3 Introduction Environmental protection MGE UPS SYSTEMS has implemented an environmental-protection policy. Products are developed accordi ng to an eco-design approach. Subst ances This product does not contain CFCs, HCFCs or asbestos.
34008030EN /AA - Page 4 Introduction Pictograms Important instructions that must always be followed. Information, advice, help. Visual indication. Action.
34008030E N/AA - Page 5 Contents 1. Present ation 1.1 St andard positions ..... .............. .............. ................ .............. .............. ............... .............. ............ 7 T ower position ............ .............. ....
34008030EN /AA - Page 6 Contents 5. T roubleshooting 5.1 T roubleshooting LEDS (21) and (22) ............. .............. .............. .............. .............. ................. ... 28 5.2 T rouble shooting not requir ing MG E UPS SYSTEMS af ter-sales support .
34008030E N/AA - Page 7 1. Presentation 1.1 Standard positions Tower position Rack position Dimensions (H x W x D) in mm / Inches Pulsar MX 4000 RT 444.5 x 131 x 700 / 17.5 x 5.16 x 27.56 Pulsar MX 5000 RT 444.5 x 131 x 700 / 17.5 x 5.16 x 27.56 Pulsar MX EXB RT 444.
34008030EN /AA - Page 8 1. Presentation 1.2 Rear panels Pulsar MX 4000 RT / 5000 RT Pulsar MX EXB RT (optional battery module) (1) Two groups of 2 programmable (10A) outlets for connection of equipmen.
34008030E N/AA - Page 9 1. Presentation 1.3 Display and control panel 1.4 Options Rack mounting kit (20) Load protected LED (21) Downgraded operation LED (22) Load not protected LED (23) Alphanumeric .
34008030EN /AA - Page 10 1. Presentation ModularEasy Pulsar MX ModularEasy enables parallel operation when combining two Pulsar MX UPSs. Consequently you can enhance the availbility level of your equipment (N+1 redundancy). You can also double your secured power capacity according to your needs (migration, netwo rk extension.
34008030EN /AA - Page 11 1. Presentation Battery extensions for UPS ba ckup times up to 80 minutes (at full load) Pulsar MX RT offers a standard backup time of 5/7 minutes at f ull load. To increase backup time, it is possible to connect Pulsar MX EXB RT modules to the UPSs.
34008030EN /AA - Page 12 2. Installation 2.1 Unpacking and contents check 2.2 Internal battery connection (Battery start-up) (40) Pulsar MX 4000 or 5000 UPS. (41) T wo sets of tower stands. (42) RS232 communications cable (43) Product documentation. (44) 4 cable lockers.
34008030EN /AA - Page 13 2. Installation 2.3 Installation in tower position Follow steps 1 to 3 to adjust the tower stands for the upright position. Always keep 150 mm free space behind the UPS rear pa nel. The distance between the tower stan ds should be 450 mm.
34008030EN /AA - Page 14 2. Installation 2.4 Installation in rack position Adjustment of the orientation of the logo and control panel UPS module rack mounting (optional rails required) Pulsar MX RT is very heavy.
34008030EN /AA - Page 15 2. Installation UPS or battery module rack mounting (optional rails required) It is not allowed to install the UPS or battery module in a hermetically closed environment without any exchan ge of air. Follow steps 1 to 4 for rack mo unting the UPS onto the rails.
34008030EN /AA - Page 16 2. Installation 2.5 Communication ports Pulsar MX RT provides 3 communication met hods that can be used simultaneou sly: ◗ 2 COM ports provide RS232 or USB comm unications using MGE UPS SYSTEMS SHUT protocol. Compatible with most power management software applications available into the enclosed Solution Pac C D-Rom.
34008030EN /AA - Page 17 2. Installation Remote Power Off communication port (16) (see page 8) Installation of communication cards (optional, standard with the NetPack version) Installation of a Remote Power Off function must be carried out in compliance with applicable regula tions.
34008030EN /AA - Page 18 2. Installation 2.6 Required protective devi ces and cable cross-sections Recommended upstream protection Recommended downstream protection Required cable cross-sections ◗ Terminal-block c able cap acity: 6 mm 2 , solid or stranded wire (maximum 8 mm 2 or AWG 8).
34008030EN /AA - Page 19 2. Installation 2.7 Connection of input/output power cables on UPS terminals ◗ This type of connection must be carried out by qualified electrical pe rsonnel.
34008030EN /AA - Page 20 2. Installation 2.8 Connection of IEC cabl es to output receptacles 1 - Connect the equipments to the UPS using the cables (49) . It is preferable to connect the priority equipments to the four outlets (2) and the non priority equipments to the four outlets (1) that can be programmed in pairs (1 and 2).
34008030EN /AA - Page 21 3. Operation 3.1 Initial start-up UPS personalisa tion 3.2 Final start-up sequence It is essential to contact our Customer Se rvice to ensure that your system is commissionned in complete safety and to benefit from the manufacturer’s guarantee.
34008030EN /AA - Page 22 3. Operation 3.3 Operating modes Normal mode Eco mode This is the standard operating mode, set by default in the factory. Under normal condition (Normal AC source available): LED (20) is ON. LEDs (30) , (32) , (34) are green. The equipments are protected by the U PS.
34008030EN /AA - Page 23 3. Operation 3.4 Operation on battery power When the Normal AC source is not available, the load continues to be protected by the UPS. Power is supplied by the battery. T ransfer to battery power Low battery wa rning End of backup time 3.
34008030EN /AA - Page 24 3. Operation 3.6 UPS shutdown 1 - Press the " 0 " button (28) more than 3s. The buzzer beeps once, and the load is no longer protected by the UPS. It is powered via the Normal AC source. If the UPS is set in frequency converter mode, the equipments will not be powered.
34008030EN /AA - Page 25 4. Access to measurements and personalisation data 4.1 Display organisation 4.2 Access to measurements 4.3 Access to UPS set- up and maintenance usin g the control panel (23) Press the scroll button (24) (see section 1.3, page 9) to access measurements for voltage, current, frequency, power output and battery capacity.
34008030EN /AA - Page 26 4. Access to measurements and personalisation data 4.4 UPS set-up Local settings Output settings ON/OFF setting s Function Factory setting Options Language English French, Ger.
34008030EN /AA - Page 27 4. Access to measurements and personalisation data Battery settings 4.5 Maintenance 4.6 Personalisation us ing external software Function Factory setting Options Comments Auto.
34008030EN /AA - Page 28 5. Troubleshooting 5.1 Troubleshooting LE DS (21) and (22) 5.2 Troubleshooting not requiring MG E UPS SYSTEMS after-sales support If LED (21) is ON: the equipments are protected by the UPS but the operation is downg raded. If LED (22) is ON: the equipments are no longer protected by the UPS.
34008030EN /AA - Page 29 5. Troubleshooting 5.3 Troubleshooting requiring MGE UPS SYSTEMS after-sales support T roubleshooting one UPS (or two UPS in p arallel) with ModularEasy modul e: Display Signification Correction POWER MODULE FAULT Internal power sub-module fault detected.
34008030EN /AA - Page 30 6. Life Cycle Monitoring (LCM) 6.1 Description This function, emb edded in the UPS, displays messag es, on screen and communica tion channels, at every imp ortant stage of the.
34008030EN /AA - Page 31 6. Life Cycle Monitoring (LCM) Reset or disable LCM In case of any LCM messages displayed: ◗ For temporary reset: press the escape button (24) more than 3 seconds, into Status and Alarm screen , to cancel temporary the alarm status.
34008030EN /AA - Page 32 7. Maintenance 7.1 Hot swapping the power sub-module Disconnecting the pow er sub-module : Reconnecting the powe r sub-module : 7.2 Hot swapping the battery sub-module Disconnecting the battery sub-module : This operation must be carried out by qualified electrical pers onnel only.
34008030EN /AA - Page 33 7. Maintenance Reconnecting the battery sub-module : 7.3 Maintenance on a UPS equipped with the ModularEasy MX module Carry out the above instructions in reverse order. ◗ To ensure safety and high performance, u se only batteries supplied by MGE UPS SYSTEMS.
34008030EN /AA - Page 34 7. Maintenance 7.4 Training centre To fully master operation of your MG E UPS SYSTEMS product and carry out level 1 servicing, see our complete range of technical training courses, avai lable in both French and English.
34008030EN /AA - Page 35 8. Appendices 8.1 Technical specifications (1) If the output voltage is 200V - 250V, the output power is 450 0VA / 4000W. (2) With one EXB module o r more, the standard output power is 5000VA / 4000W. (3) Values for 70% / 100% of UPS output.
34008030EN /AA - Page 36 8. Appendices 8.2 Glossary Backup time Time that the connected equipments can operate on battery power. Bypass AC source Source supplying the bypass li ne. The equipments can be transfe rred to the bypass line if an overload occurs on the UPS output, for maintenance or in the event of a malfunction.
34008030EN /AA - Page 37.
34008030EN /AA MGE UPS SYSTEMS T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R 140, Avenue Jean Kuntzmann ZIRST - M ontbonno t St Martin 38334 - Saint Ismier Cedex - Fr ance www.
Een belangrijk punt na aankoop van elk apparaat MGE UPS Systems 4000 RT (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen MGE UPS Systems 4000 RT heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens MGE UPS Systems 4000 RT vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding MGE UPS Systems 4000 RT leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over MGE UPS Systems 4000 RT krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van MGE UPS Systems 4000 RT bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de MGE UPS Systems 4000 RT kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met MGE UPS Systems 4000 RT . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.