Brunel Mk III Conventional Flue With upgradeable control valve Instructions for Use, Installation and Servicing For use in GB, IE (Great Britain and Eire) PR0595 Issue 4 (August 2008) IMPOR T ANT Do not attempt to burn rubbish in this fire. This stove must only be operated with the door secured firmly in position.
2 CONTENTS COVERING THE FOLLOWING MODELS BRUNEL - 8050 - P8050 PAGE APPLIANCE COMMISIONING CHECKLIST 3 USER INSTRUCTIONS 4 INSTALLATION INSTRUCTIONS 8 Technical Specifications 8 Site Requirements 9 In.
3 FLUE CHECK PASS FAIL 1. Flue is correct for appliance 2. Flue flow test 3. Spillage test GAS CHECK 1. Gas soundness & let by test 2. Standing pressure test mb 3. Appliance working pressure (on High Setting) mb NB All other gas appliances must be operating on full 4.
4 USER INSTRUCTIONS 2.3 • Holdin for 5to 10seconds and thenrelease The pilot remains lit. If the pilot does not light, repeat the procedure.
5 4.2 • Holdin the controlknob androtate anti-clockwise until the knob is pointing at the ignition symbol ( ★ ) • Applya lightedmatch tothe pilothood, Diagram 3 3 AR0897 4.
6 USER INSTRUCTIONS AR0900 6 6.4 • Placethree coals equallyspaced onthe rear ofthe fuel bed so they touch the rear panel, Diagram 7 AR0901 7 6.
7 USER INSTRUCTIONS 9. 'RUNNING IN' 9.1 The surface coating on your GAZCO stove will ‘burn off’ during the first 24 hours of operation on high, producing a harmless and temporary odour. If the odour persists ask your retail for advice. 10.
8 INSTALLATION INSTRUCTIONS TECHNICAL SPECIFICATION Covering the following models Brunel - 8050 - P8050 Model Gas Cat. Gas Type Pressure Nox Class Aeration Injector Gas Rate m 3 / h Input kW (Gros) Country Hoog Laag Brunel 8050 I 2H Natural Gas (G20) 20mbar 5 4 x 16 120 0.
9 INSTALLATION INSTRUCTIONS SITE REQUIREMENTS 1. FLUE AND CHIMNEY REQUIREMENTS 1.1 The chimney or flue system must comply with the rules in force, and must be a minimum of 127mm (5”) in diameter. The following are suitable for use with this appliance.
10 2.3 Having run the gas supply to the stove, PURGE THE SUPPLY PIPE, this is essential to expel any debris that may block the gas controls. • Connectthe gassupply tothe 8mm-compressionelbow at the RH rear corner of the stove, Diagram 3.
11 AR0886 4 2.7 • Placethe closure plateagainst thefireplace opening • • Ensurethere is sufficientoverlap aroundthe perimeter to allow a fume tight seal to be made • Cutstraight acrossthe topof theplate if trimmingis required 2.
12 3.5 • Placefive coals onthe frontof the fuelbed sothey rest on the front coal effect and lean against the vertical fingers, Diagram 9 AR0902 9 3.
13 INSTALLATION INSTRUCTIONS COMMISSIONING 1. COMMISSIONING 1.1 • Closeall openable doorsand windowsin the room • Ignitethe stoveand operateon maximum for10 minutes AR0539 1 If there is any doubt, run the stove for a further 10 minutes, and repeat the test.
14 IGNITION FUNCTIONAL CHECK 1 PILOT WILL NOT LIGHT Ensure there is no debris around the pilot assembly, (e.g. soot, etc.) which could short the spark, clean the area. Operate the valve. Is there a spark? Consult Section 2 and retry. Check alignment of pilot burner head, change the ignition lead, see diagram 1 on page 17.
15 SERVICING INSTRUCTIONS FAULT FINDING CHARTS PILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USE Ensure there is no debris around the pilot assembly, e.g. coal, soot etc. which could short the spark, clean the area. Problem is with the pipework or fittings which lead to the fire.
16 3. IGNITION LEAD AND PIEZO Due to the method of manufacture, these components can only be replaced as an integral unit. 3.1 • Turnthe gas supplyoff atthe isolation d.
17 AR0320 3 • Prisethe smallretaining ringout ofthe inlet andremove the filter 4.2 • Replacewith a newfilter andpush into positionensuring that it sits on the shoulder • Replacethe retainingring andpush intoposition.
18 8. PRIMARY AERATION PLATE 8.1 • Turnthe gas supplyoff atthe isolation device. 8.2 To open the doors: • Slackenthe domednut onthe upperdoor and loosen the bolt from behind the latch 8.
19 SERVICE RECORDS 1ST SERVICE 2ND SERVICE Date of Service: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Date of Service: ................................. Next Service due: ............................... N e x t S e r v i c e d u e : .
Gazco Limited, Osprey Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7JG Tel: (01392) 261999 Fax: (01392) 444148 E-mail: info@gazco.com A member of the Stovax Group.
Een belangrijk punt na aankoop van elk apparaat Stovax P8050 (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Stovax P8050 heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Stovax P8050 vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Stovax P8050 leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Stovax P8050 krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Stovax P8050 bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Stovax P8050 kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Stovax P8050 . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.