Application Guide M-2299 Adapter Panel.
Adapter Panel M-2299 CONTROLS Adapts M-2001 Series Digital T apchanger Contr ol to Replace T oshiba TB-R800 Regulators • Connects easily to the M-2001 Series Digital T apchanger Control using mounti.
The M-2299 is an adapter panel which, when combined with the M-2001 Series Digital Tapchanger Control, provides convenient direct replacement of Toshiba TB-R800 regulators. The M-2299 mounts into the control cabinet using the same two hinge pins which must be saved from the original regulator.
WARNING DANGEROUS V OL T A GES , ca pable of causing death or serious injur y , are present on the e xter nal ter minals and inside the equip- ment. Use extreme caution and follo w all safety r ules when han- dling, testing or adjusting the equipment.
PRODUCT CAUTIONS Before attempting any test, calibration, or maintenance procedure, personnel must be completely familiar with the particular circuitry of this unit, and have an adequate understanding of field effect devices.
T ABLE OF CONTENTS M-2299 Adapter Panel Application Guide 1.0 Description ................................................................................................................... 1 Standard Features .........................................
5.0 Test Procedures ........................................................................................................ 1 0 Equipment Required .................................................................................................. 1 0 Setup Procedure .
–1– M-2299 Application Guide The Beckwith Electric M-2299 Adapter Panel, used in conjunction with the M-2001 Series Digital Tapchanger Control, uses modern electronic digital design and digital processing circuitry to achieve an overall stability and resolution unattainable with electromechanical and analog design tapchanger controls.
–2– M-2299 Application Guide 2.0 Installation The M-2299 has hinges on the right side that allow easy mounting into the existing Toshiba regulator cabinet. Refer to Figure 1, below. 2 . 1 Removal of the Toshiba Regulator Refer to Figure 1, and Figure 3, Outline Dimensions.
–3– M-2299 Application Guide 2 . 2 Installation of the M-2001 Series Digital Tapchanger Control Mount the M-2001 Tapchanger Control to the back of the M-2299 Adapter Panel and secure with the four screws provided. The four screws are shipped in a drawstring bag which is attached to the adapter panel.
–4– M-2299 Application Guide CO . I NC EL E CT RI C BE CK WI T H TEST TERMINAL 3 AMP VOLTAGE .25 AMP MOTOR POWER 6 AMP VOLTAGE IN METER OUT AUTO MANUAL LOWER RAISE INT EXT VOLTAGE SOURCE M-2299 . NEUTRAL LIGHT T APCHANGER CONTROL OFF OFF OFF B D - M DOWN 01 20 UP U ENTER E COM 2 OK R O E R L VP W E WR A RE IS 12.
–5– M-2299 Application Guide M-2001 Customer T erminal Block Circuit Board T erminal Block Connections TB-1 T o T apchanger BT1 TB1-8 TB1-15 C1-2 C1-1 TB1-13 TB1-1 1 TB1-4 TB1-10 TB1-9 TB1-14 C1-2.
–6– M-2299 Application Guide 2 .4 Lightning Protection It has been determined that transient voltages in excess of 1500 V ac rms can exist on the “ground” lead normally tied to TB1-8 on the printed circuit board.
–7– M-2299 Application Guide M-2299 ADAPTER P ANEL FUNCTIONS TB1 VOL T AGE REDUCTION STEP #2 CONT ACT VOL T AGE REDUCTION STEP #1 CONT ACT NEUTRAL LIGHT SWITCH OPERA TIONS COUNTER SWITCH LINE CURR.
–8– M-2299 Application Guide 3.1 Features Neutral Light Circuit The M-2299 is prepared for use with regulators which use a neutral light. Toshiba products require that the Neutral Light terminal TB1-11 (BT-5) be grounded when the light is to be illuminated.
–9– M-2299 Application Guide * * TB1-1 1 TB1-12 TB1-6 TB1-10 TB1-7 TB1-9 MOTOR SUPPL Y T APCHANGER CONTROL M-0329 90 BACKUP LOWER BLK RAISE BLK LOWER 84L 84R 120 V AC POWER 3 2 4 14 15 REGULA TED .
–10– M-2299 Application Guide 4 . 0 M-2001 Tapchanger Control Software Settings Adjust the BANDCENTER setting to the nominal voltage desired. Adjust the BANDWIDTH setting to the desired voltage band, centered on the Bandcenter setpoint, that the voltage must exceed before timer and subsequent tapchanger operation occurs.
–11– M-2299 Application Guide 5 . 1 Bench Test NO TE: This test assumes that the M-2001 T apchanger Control is connected to the M-2299 Adapter P anel. 1. Apply 120.0 V ac from power source. 2 . The display of the M-2001 will automatically advance to Local Voltage screen.
–12– M-2299 Application Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 27 Contact Wetting Supply (+12 V dc) V oltage Reduction Step #2 Input T apchanger Raise Output T apchanger Lower Output V oltage R.
–13– M-2299 Application Guide 5 . 2 M-2001 Checkout Procedure NO TE: This test of the M-2001 assumes that the unit remains connected to the adapter panel. Basic Operational Test 1. Apply 120.0 V ac to TB1-9 (motor power) and TB1-10 regulated voltage) of adapter panel.
–14– M-2299 Application Guide M-2299 T APCHANGER CONTROL TB1 on printed circuit board 14 15 LOAD CURRENT AUX CT A 5 A 200 mA 3 4 LDC-CT XXXX:5 A Shorting device Normally 1-CT on X , X , X bushing 123 N/U N/U Figure 8 Setup for Current Checkout Procedure 3.
–15– M-2299 Application Guide 6 . 2 Voltage Source Switch The VOLTAGE SOURCE switch will disconnect all power from the unit when in the EXT position with no source connected to the front panel voltage and motor power inputs. ▲ CAUTION: Do not reverse the ground and hot wires when connecting an external source.
–16– M-2299 Application Guide This P age Left Intentionally Blank.
Legal Information Patent The units described in this manual are covered by U.S. Patents, with other patents pending. Buyer shall hold har mless and indemnify the Seller , its directors, officers, agen.
I S O 9 0 0 1 : 2 0 0 0 R e g i s t e r e d BECKWITH ELECTRIC CO ., INC. 6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A. PHONE (727) 544-2326 • FAX (727) 546-0121 E-MAIL marketing@beckwithelectric.com WEB PAGE www.beckwithelectric.com © 2001 Beckwith Electric Co.
Een belangrijk punt na aankoop van elk apparaat Toshiba M-2001 Series (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen Toshiba M-2001 Series heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens Toshiba M-2001 Series vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding Toshiba M-2001 Series leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over Toshiba M-2001 Series krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van Toshiba M-2001 Series bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de Toshiba M-2001 Series kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met Toshiba M-2001 Series . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.