ADC F/UTP Riser Cable

4 pagina's·199 KB·Netwerkrouter·PDF·EN
ADC F/UTP Riser Cable
Inhoudsopgave 5 secties TrueNet ® · CopperTen ® Four Pair F/UTP Riser Cable · Features: · Spec Sheet · … TonenVerbergen
Page 1 of the ADC F/UTP Riser Cable user manual — Spec Sheet
Pagina 1 · klik om te vergroten
Pagina 1

TrueNet ®

CopperTen ® Four Pair F/UTP Riser Cable

ADC F/UTP Riser Cable — TrueNet ® diagram (page 1)
Afb. 1 · TrueNet ®

ADC F/UTP CopperTen® cable can be used in data center, communications closet and work station for 10G shielded performance. Installed in high-performance networks world wide, the system’s design minimizes alien crosstalk and insertion loss and meets the performance requirements of IEEE 802.3an, ISO 11801 Class EA and TIA/EIA-568-B.2-10 standards

Features:

Supports 10 Gigabit Ethernet over shielded copper to a full 100 meters •

20 year TrueNet CopperTen warranty •

Spec Sheet

  • w w w . a d c . c o m
  • + 1 - 9 5 2 - 9 3 8 - 8 0 8 0
  • 1 - 8 0 0 - 3 6 6 - 3 8 9 1
Page 2 of the ADC F/UTP Riser Cable user manual — TrueNet ®
Pagina 2 · klik om te vergroten
Pagina 2

TrueNet ®

CopperTen ® Four Pair F/UTP Riser Cable

Specifications

4 / 0 8 • 1 0 4 7 4 4 A E CopperTen® Four Pair F/UTP Riser Cable

CONSTRUCTION Conductor: 23 AWG solid bare copper Insulation: HDPE Separator: HDPE Shield: Aluminum/polyester foil Drain Wire: Stranded tinnned copper Jacket: Lead free, flame retardant PVC Nominal O.D.:.280" (7.1mm)

COMPLIANCES UL Subject 444 (UL)-C(UL) Type CMR ICEA S-90-661 NEC 800 Type CMR TIA/EIA-568-B.2-1 Category 6 Horizontal Cable Requirements TIA/EIA-568-B.2-10 Augmented Category 6 Horizontal Cable Requirements ISO/IEC 11801 Category 6 Horizontal Cable Requirements ISO/IEC 11801 Category 6a Horizontal Cable Requirements

COMMON APPLICATIONS 4/16 Mb/s Token Ring (IEEE 802.5) 52/155 Mb/s ATM (ATM Forum) 10BASE-T (IEEE 802.3) 622 Mb/s ATM (ATM Forum) 100 Mb/s TP-PMD 1000BASE-T (Gigabit Ethernet) Broadband & Baseband Video 1 Gigabit Networking System (WGNA) 100BASE-T (“Fast Ethernet”) 1.2 Gb/s ATM (ATM Forum) 100BASE-T4 (“Fast Ethernet”) 77 Channel Broadband Video 100BASE-TX (“Fast Ethernet”) 10GBASE-T Ethernet (IEEE 802.3an) 100VG-Any LAN (IEEE 802.12)

THERMAL CHARACTERISTICS Transport and Storage: -10°C to 60°C Installation: 4°C to 50°C Operation: -10°C to 60°C

MECHANICAL CHARACTERISTICS Bend RadiusDuring Installation: 8 X O.D. Installed: 4 X O.D. Pull Tension: 25# (110N)

ELECTRICAL CHARACTERISTICS Conductor DC Resistance @ 20°C (Max): 28.6 Ω/1000 ft (9.38 Ω/100 m) DC Resistance Unbalance (Max): 5% Mutual Capacitance @ 20°C (Max): 17 pF/ft (5.6nF/100 m) Operating Voltage (Max): 300 VDC Worst Case Cable Skew: 45 ns/100 m Nominal Velocity of Propagation: 72%

  • 2 w w w . a d c . c o m
  • + 1 - 9 5 2 - 9 3 8 - 8 0 8 0
  • 1 - 8 0 0 - 3 6 6 - 3 8 9 1
Page 3 of the ADC F/UTP Riser Cable user manual — TrueNet ®
Pagina 3 · klik om te vergroten
Pagina 3

TrueNet ®

CopperTen ® Four Pair F/UTP Riser Cable

FREQ MHZFitted Impedance OhmsInsertion Loss dB/100mReturn Loss dB/100mPair-Pair NEXT dB/100mPSNEXT dB/100m SpecMaxSpecMinSpecMinSpecMinSpec 1100 +/- 151.72.024.320.085.974.383.272.3 4100 +/- 153.43.727.123.075.965.373.063.3 8100 +/- 154.85.229.424.568.660.865.458.8 10100 +/- 155.45.931.025.061.559.359.157.3 16100 +/- 156.87.430.425.063.656.262.754.2 20100 +/- 157.68.331.625.065.454.862.752.8 25100 +/- 158.69.333.124.362.653.358.651.3 31.25100 +/- 159.710.434.223.667.151.963.549.9 62.5100 +/- 1513.914.931.121.554.047.452.545.4 100100 +/- 1517.919.028.920.152.744.350.742.3 155100 +/- 1522.624.033.018.845.341.444.739.4 200100 +/- 1526.127.523.518.050.739.848.737.8 250100 +/- 1529.431.022.917.342.338.341.136.3 300100 +/- 1532.734.226.216.843.137.140.535.1 350100 +/- 1535.837.222.916.345.236.142.234.1 400100 +/- 1538.740.021.915.944.735.341.433.3 450100 +/- 1541.542.722.415.539.234.537.832.5 500100 +/- 1544.145.320.115.236.733.835.231.8 550100 +/- 1546.9-21.7-39.9-38.6- 600100 +/- 1549.5-17.0-36.6-34.4-

4 / 0 8 • 1 0 4 7 4 4 A E CopperTen® Four Pair F/UTP Riser Cable

  • 3 w w w . a d c . c o m
  • + 1 - 9 5 2 - 9 3 8 - 8 0 8 0
  • 1 - 8 0 0 - 3 6 6 - 3 8 9 1
Page 4 of the ADC F/UTP Riser Cable user manual — Specifications
Pagina 4 · klik om te vergroten
Pagina 4
FREQ Pair-Pair ACR PSACR Pair-Pair ELFEXT PSNEXT LCL MHZ dB/100m Max Spec Min Spec Min Spec Min Spec Spec 1 84.2 72.3 81.5 70.3 83.8 67.8 83.1 64.8 40.0 4 72.7 61.5 69.8 59.5 75.8 55.8 75.2 52.8 40.0 8 64.1 55.5 60.9 53.5 64.2 49.7 62.5 46.7 40.0 10 56.5 53.4 54.0 51.4 64.0 47.8 60.3 44.8 40.0 16 57.2 48.8 56.3 46.8 63.7 43.7 61.2 40.7 38.0 20 58.1 46.5 55.1 44.5 59.9 41.8 58.4 38.8 37.0 25 54.4 44.0 50.4 42.0 57.5 39.8 56.9 36.8 36.0 31.25 57.5 41.5 53.8 39.5 55.4 37.9 55.6 34.9 35.1 62.5 40.8 32.5 39.3 30.5 52.4 31.9 50.6 28.9 32.0 100 35.7 25.3 33.4 23.3 52.9 27.8 51.1 24.8 30.0 155 23.7 17.5 22.1 15.5 45.4 24.0 43.8 21.0 28.1 200 25.8 12.3 23.8 10.3 46.0 21.8 43.4 18.8 27.0 250 14.2 7.4 12.5 5.4 43.0 19.8 41.0 16.8 26.0 300 11.9 3.0 9.3 1.0 43.0 18.3 39.3 15.3 - 350 11.0 -1.0 8.1 -3.0 39.0 16.9 38.3 13.9 - 400 7.5 -4.7 3.4 -6.7 37.5 15.8 35.7 12.8 - 450 -0.7 -8.2 -2.2 -10.2 38.9 14.7 36.2 11.7 - 500 -5.7 -11.4 -7.2 -13.4 39.5 13.8 35.4 10.8 - 550 -5.6 - -6.9 - 31.9 - 32.3 - - 600 -12.9 - -14.4 - 31.2 - 29.2 - - NOTE: The above listed discrete frequency electrical performance values are provided for engineering information only. Actual compliance testing is based on swept frequency measurements. The spec values are based on TIA/EIA568-B.2-10 specification. Sheet O r d e r i n g I n f o r m a t i o n Description Catalog Number 1000 foot reel, 41lbs 61kg 10G-A6TRF-XX02 Spec NOTES: XX = Jacket color - BL = Blue, WT = White, GY = GrayPair-Pair ACR dB/100mPSACR dB/100mPair-Pair ELFEXT dB/100mPSNEXT dB/100mLCL dB/100m MaxSpecMinSpecMinSpecMinSpecSpec 84.272.381.570.383.867.883.164.840.0 72.761.569.859.575.855.875.252.840.0 64.155.560.953.564.249.762.546.740.0 56.553.454.051.464.047.860.344.840.0 57.248.856.346.863.743.761.240.738.0 58.146.555.144.559.941.858.438.837.0 54.444.050.442.057.539.856.936.836.0 57.541.553.839.555.437.955.634.935.1 40.832.539.330.552.431.950.628.932.0 35.725.333.423.352.927.851.124.830.0 23.717.522.115.545.424.043.821.028.1 25.812.323.810.346.021.843.418.827.0 14.27.412.55.443.019.841.016.826.0 11.93.09.31.043.018.339.315.3- 11.0-1.08.1-3.039.016.938.313.9- 7.5-4.73.4-6.737.515.835.712.8- -0.7-8.2-2.2-10.238.914.736.211.7- -5.7-11.4-7.2-13.439.513.835.410.8- -5.6--6.9-31.9-32.3-- -12.9--14.4-31.2-29.2-- Website: www.adc.com From North America, Call Toll Free: 1-800-366-3891 • Outside of North America: +1-952-938-8080 Fax: +1-952-917-3237 • For a listing of ADC’s global sales office locations, please refer to our website. ADC Telecommunications, Inc., P.O. Box 1101, Minneapolis, Minnesota USA 55440-1101 Specifications published here are current as of the date of publication of this document. Because we are continuously improving our products, ADC reserves the right to change specifications without prior notice. At any time, you may verify product specifications by contacting our headquarters office in Minneapolis. ADC Telecommunications, Inc. views its patent portfolio as an important corporate asset and vigorously enforces its patents. Products or features contained herein may be covered by one or more U.S. or foreign patents. An Equal Opportunity Employer 104744AE 4/08 Revision © 2008, 2007 ADC Telecommunications, Inc. All Rights Reserved

Vraag stellen over de ADC F/UTP Riser Cable

Eigenaren en ons team reageren doorgaans binnen een dag — en uw vraag helpt ook de volgende persoon.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Nog geen vragen over de ADC F/UTP Riser Cable

Stel als eerste een vraag — andere eigenaren of ons team geven antwoord.

Origineel document

ADC F/UTP Riser Cable handleiding-pdf

4 pagina's·199 KB·Netwerkrouter·PDF
Klik op een bovenstaande pagina om deze hier te openen
Pagina 1 / …
100%
Pagina's laden…