Printed in U.S.A. 1/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Application DuraDrive Direct Coupled Actuators are designed to be used in both damper and valve control ap plications. The following general instruction s ar e for damper applications, refer to the Applicable Liter ature table for valve literature.
2 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Applicable Literature SPECIFICA TIONS Inputs Control Signal: 4 to 20 mAdc (with the addition of a 50 0 Ohm re sistor - not included) or 2 to 10 Vdc. See Figure-1 through Figure - 8.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 3 Minimum Damper Shaf t Length, Stan da rd Da mper shaft must be at least 4-5/8" (1 17 mm) long for standard mounting. Optional Shorter than standard length shafts require the AM-676 shaft extension (order separately).
4 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 TYPICAL APPLICA TIONS (wiring diagrams) MS40-7170 Black White L1 L2 120 Vac GRD Green/Yellow 2 to 10 Vdc Yellow/Black Gray AI COM .
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 5 MS40-7171 Brown Light Blue L1 L2 240 Vac GRD Green/Yellow Yellow/Black Gray AI COM 2 to 10 Vdc + - Control Signal 1 Position Feedb.
6 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 MS40-7173 Red Black 24H (DC+) 24G (DC-) 24 Vac Transformer or 22-30 Vdc GRD Green/Yellow 4 to 20 mA Yellow/Black Gray AI COM + - 5.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 7 INST ALLA TION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately . If undamaged, open the package and inspect the device for obvious damage.
8 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Precautions General War ni ng : • Electrical shock hazard! Disconnect the powe r supply (line power) before and during installation to prevent electric shock and equipment damage.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 9 Mounting Mount th e T AC DuraDrive Actuator directly on the damper shaft in locati ons that clear th e maximum dimensions of the actuator case and allow the actu ator to be mounted flush to the surface of the terminal box and perpendicular to the damper shaft.
10 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Mounting the Actuator f or Clockwise or Counterc lockwise Dampers The zero (0) position on the posi tion indicator is the normal or spring return po sition.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 11 Figure-10 Long Damper Shaft Mounting with Clockwise Spring Return for Normally Cl osed Damper. R 1 1 5 CENTERLINE 1 Two AM-754 Universal Mounting Clamp Assemblies are provided with each actuator.
12 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Figure-11 Lon g Damper Shaft Mounting with Counterclockwise Spring Return for Normally Closed Damper. 1 5 CENTERLINE 1 Two AM-754 Universal Mounting Clamp Assemblies are provided with each actuator.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 13 Short Damper Shafts See Figure-13 for installation of actuator using the AM-676 Un iversal Shaft Extension.
14 © Copyright 2010 Schneider Electric All Rights Reserved. F-26748-6 Wiring Requirement s Control and Power Leads Remove blue plastic thread protectors b efore installing conduit fittings. See Figure-1 throug h Figure 8 for typical wiring applications and T able-3 for maximum wire lengths.
F-26748-6 © Copyright 2010 Schneider Electric All Rights Reserved. 15 CHECKOUT This procedure is for checking out a normally closed actuator that is typically moun ted unpowered. It is possible to mount the actuato r with power applied for special applications.
Copyright 2010, Schneider Ele ctric All brand names, trademarks and regist ered trademarks are the property of t heir respective owners. Information cont ained within this document is subject to chang e without notice. F-26748-6 www .schneider-electric.
Een belangrijk punt na aankoop van elk apparaat 3Com MS40-717X (of zelfs voordat je het koopt) is om de handleiding te lezen. Dit moeten wij doen vanwege een paar simpele redenen:
Als u nog geen 3Com MS40-717X heb gekocht dan nu is een goed moment om kennis te maken met de basisgegevens van het product. Eerst kijk dan naar de eerste pagina\'s van de handleiding, die je hierboven vindt. Je moet daar de belangrijkste technische gegevens 3Com MS40-717X vinden. Op dit manier kan je controleren of het apparaat aan jouw behoeften voldoet. Op de volgende pagina's van de handleiding 3Com MS40-717X leer je over alle kenmerken van het product en krijg je informatie over de werking. De informatie die je over 3Com MS40-717X krijgt, zal je zeker helpen om een besluit over de aankoop te nemen.
In een situatie waarin je al een beziter van 3Com MS40-717X bent, maar toch heb je de instructies niet gelezen, moet je het doen voor de hierboven beschreven redenen. Je zult dan weten of je goed de alle beschikbare functies heb gebruikt, en of je fouten heb gemaakt die het leven van de 3Com MS40-717X kunnen verkorten.
Maar de belangrijkste taak van de handleiding is om de gebruiker bij het oplossen van problemen te helpen met 3Com MS40-717X . Bijna altijd, zal je daar het vinden Troubleshooting met de meest voorkomende storingen en defecten #MANUAl# samen met de instructies over hun opplosinge. Zelfs als je zelf niet kan om het probleem op te lossen, zal de instructie je de weg wijzen naar verdere andere procedure, bijv. door contact met de klantenservice of het dichtstbijzijnde servicecentrum.